Volume by Tracer Dilution
All quantities are live and update with your inputs.
Operating Conditions
- Tracer
- PTSA
- System
- Cooling tower
- Added
- 50.0 g
- Background
- 0 ppb
- After
- 100 ppb
- Recirc
- none
Key Results
Primary outputs and operational context based on your inputs.
Based on a rise of 100 ppb; a ±1 ppb reading error changes this by ±1.0%.
System Volume The dilution solved backward, to three significant figures.
13,200 gal
13,209 gal unrounded, 50,000 L
PTSA into a cooling tower, to three significant figures.
Tracer Added The active tracer that went in, on the basis the kit reads.
5.00 g PTSA
50.0 g as added
Solution grams times the active fraction.
Rise After mixing less background, in the reading's unit.
100 ppb
0 → 100 ppb
Clear of the 1 ppb resolution.
Uncertainty What a one-resolution reading error does to the answer.
±1.0 %
per 1 ppb of reading error
About ±132 gal either way.
Rule of Thumb Three times the recirculation rate, the tower rule of thumb.
n/a
enter a recirculation rate
The classic estimate is three times the recirculation rate.
Before You Trust It The procedure decides whether the number is right.
- Towers: stop the blowdown for the test. Blowdown removes tracer and makes the system look bigger.
- Wait for full mixing. Towers 15 to 30 minutes, large loops an hour or more, two readings within 5%.
- Read the background first with the feed paused, and subtract it.